EthMBus-5 SMART, X-Port line
Ethernet to M-Bus communication converter
|
|
|
Converter for SMART metering
Designed for remote communication with M-Bus meters using the Ethernet computer network in industry and building automation.
In the Smart M-Bus mode the converter works as a server.
It communicates with the M-Bus meters independently, processes their data and stores it in its own memory.
The meter data is simultaneously available in form of:
- table on a webpage
- xml, xml(REST) and csv export
- M-Bus protocol communication
- e-mail with attached xml, csv exports
- exports uploaded to an FTP server
In the basic mode the converter works as a transparent gateway for transfer of M-Bus messages using TCP or UDP Ethernet protocols.
Main characteristics
M-Bus port
- Connection of 1 to 5 M-Bus slave devices.
The most commonly used devices are heat, water, gas and electricity consumption meters.
- Surge protection warranting above standard level of protection against overvoltage.
- Current protection against overload and short circuit on the communication line with
LED status indication.
Power supply
- Wide range of power supply voltages. DC 9-39.5V or AC 9-27.5V.
- Overvoltage protection and resettable current fuse.
- LED power supply indication.
Ethernet
- TCP, UDP protocols and virtual COM port software.
- 10/100BASE-TX ethernet port, RJ45 connector.
Mechanical construction
- Aluminium box with mounting on 35 mm DIN rail.
Main software characteristics
Transparent gateway mode:
-
TCP/IP connection
- server or client mode
- backup IP addresses for connection
- connection to a web address (DNS)
- UDP connection
|
|
Smart M-Bus application mode:
- web page with meter data
- xml, xml(REST), csv exports
- e-mails with exports and service information
- exports uploaded to an FTP server
|
|
Software functions
- Configuration of the converter through a web interface or Telnet.
- TCP and UDP communication in server or client mode including
connection backup IP addresses.
- DNS support (host name instead of IP)
- Logging of Ethernet activity and error states.
- Search for meter addresses and their change (meter must support this functionality).
- Success rate statistics for communication with individual meters.
Differences from the EthMBus-5M SMART converter
- More powerful overvoltage protections on the M-Bus line and the power port.
- More powerful M-Bus line driver with more efficient filters. The length of the M-Bus line can be more then 1km.
- Wider range of operating temperatures.
- More robust mechanical construction.
References
In between years 2011-2018 more than 600 units of the Ethernet to M-Bus converters have been deployed in cooperation with the company IPECON s.r.o. for several custommers in Slovakia and Czech Republic. Converters were used to collect data from utility heat meters into SCADA systems.
Guarantee of quality
- Each converter passes through several functional electrical tests during the production.
Additionally a communication test is performed after final assembly.
- EMC certification in an accredited laboratory for industrial environment.
- Solid design and construction based on many years practical experience.
- Converters deployed with trouble free operation in various applications since 2011.
|
Communications interface | 10BASE-T or 100BASE-TX (auto-sensing) |
Communication protocols | ARP, UDP, TCP, ICMP, Telnet, TFTP, AutoIP, DHCP, HTTP, SNMP |
Connector | RJ45 |
Compatibility | Ethernet: Version 2.0/IEEE 802.3 |
Number of devices that can be connected | 1 to 5 SLAVE devices, idle current max. 7.5mA |
Baud rate | 300 - 9600 bps |
Protection | - overvoltage protection TVS 1500W |
- electronic protection against overloads and short circuit on the communication line |
note: converter can withstand sustained short circuit on the communication line |
Galvanic separation | up to 1kV from power supply, more than 1kV from Ethernet |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Recommended range of power supply voltages |
DC power supply | 9V to 39.5V |
AC power supply | 9V to 27.5V |
Maximum limits of supply voltage - permanent operation at these voltages is not recommended |
Minimum power | 8.5V DC, 8.5V AC |
Maximum power | 42.5V DC, 29.5V AC |
Protection | overvoltage protection TVS 1500W |
Power consumption | 1.7W to 3W* depending on load and power supply *short on the M-Bus line |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Power - green | indication of connected supply voltage |
Transmit - green | indication of data broadcasting on the M-Bus line |
Receive - yellow | indication of data reception on the M-Bus line |
Overload/Short - red | indication of M-Bus line overload – flashing (idle current > 8mA) |
indication of short on the M-Bus line – turned on (resistance of the line < 500Ω) |
Operating range | -40°C to 60°C |
Mechanical design | aluminium box |
Mounting | 35 mm DIN rail (EN 50022 top hat rail) |
Dimensions: height x width x length | 33 x 57 x 87 mm - without connectors |
33 x 57 x 106 mm - with connectors (M-Bus and Power plug-in connectors in the terminal blocks) |
Protection classification | IP40 |
Weight | 136g |
EMC compatibility of the M-Bus converter has been tested according to the following industrial environment standards.
Standard | Test | Level |
EN 55011 | Power line - CONDUCTED EMISSIONS 10/150 kHz - 30 MHz | Class A |
EN 55011 | RADIATED EMISSIONS (Electric Field) 30 MHz - 1000 MHz | Class A |
|
Standard | Test | Level |
EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Contact discharge | ± 4 kV |
EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Air discharge | ± Information sheet |
EN 61000-4-3 | RADIATED RADIO-FREQUENCY ELECTROMAG. FIELD 80MHz - 1GHz | 10 V/m |
EN 61000-4-3 | RADIATED RADIO-FREQUENCY ELECTROMAG. FIELD 1.4GHz - 2GHz | 10 V/m |
EN 61000-4-3 | RADIATED RADIO-FREQUENCY ELECTROMAG. FIELD 2GHz - 2.7GHz | 3 V/m |
EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - Power line | ± 4 kV |
EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - M-Bus line | ± 4 kV |
EN 61000-4-5 | SURGE IMMUNITY - Power line. Common/differential mode. | ± 1 kV / ± 1 kV |
EN 61000-4-5 | SURGE IMMUNITY - M-Bus line. Cable shielding. | ± 4 kV |
EN 61000-4-5 | SURGE IMMUNITY - M-Bus line. Common/differential mode.* | ± 4 kV / ± 2 kV |
EN 61000-4-6 | CONDUCTED DISTURBANCES, INDUCED BY RADIO-FREQUENCY | 10 V |
FIELDS 0.15MHz - 80 MHZ. Power line and M-Bus line. |
* test carried out at the request of the manufacturer.
The M-Bus port has an increased durability against overvoltage. Carrying out this type of test is not required with the use of shield cable.
|
|
End user
Price list for individuals and companies which do not buy converters for resale.
|
|
|
Integrator
Price list for companies which buy converters for the purpose of resale to their custommers as manufacturers or suppliers.
The price list is available only to registered business partners.
Registration request.
|
|
|
Promotional leaflet
|
Download
|
EthMBus5_SMART_flyer_v1_2_EN.pdf
|
20.4. 2021
|
292 kB
|
Manuals for new converters with Smart firmware
|
Short overview of modes and functions
|
Download
|
Ethernet_SMART_features_flyer_v0_13_EN.pdf
|
19.10. 2016
|
640 kB
|
|
Manual
|
Download
|
EthMBus5_SMART_manual_v1_2_EN.pdf
|
20.4. 2021
|
1.21 MB
|
|
Web Interface manual
|
Download
|
Ethernet_SMART_Web_Interface_v0_52_EN.pdf
|
29.11. 2019
|
2.29 MB
|
|
Telnet Setup manual
|
Download
|
Ethernet_SMART_Telnet_v1_29_EN.pdf
|
29.11. 2019
|
1.23 MB
|
|
Data exports manual
|
Download
|
Ethernet_SMART_exports_v1_04_EN.pdf
|
2.8. 2016
|
1.06 MB
|
Readout software
|
Excel® file for M-Bus data collection and processing
|
Download
|
JC-E_readout_v11_6_EN.xlsm
|
16.3. 2018
|
228 kB
|
|
Manual for the data collecting Excel® file
|
Download
|
JC-E_readout_xls_manual_v1_12_EN.pdf
|
11.1. 2023
|
2.13 MB
|
Legacy manuals for old converters
|
Manual EthMBus-5 (2 pin power connector, JC-e webinterface)
|
Download
|
Ethernet_MBus_5_manual_v2_8_EN.pdf
|
22.9. 2014
|
1.15 MB
|
|
Manual EthMBus-5 (old firmware, Lantronix webinterface)
|
Download
|
Ethernet_MBus_5_manual_v2_7_EN.pdf
|
24.6. 2014
|
1.13 MB
|
Note: this manual applies only to the old Lantronix firmware version
|
|
Extended Manual EthMBus-5 (old fw., Lantronix webinterface)
|
Download
|
Ethernet_MBus_5_navod_uplny_v1_4_SK.pdf
|
31.7. 2012
|
950 kB
|
Note: this manual applies only to the old Lantronix firmware version
|
Lantronix utilities
|
Top view
Typical application
Typical wiring of the converter with M-Bus devices, power supply and Ethernet network connection to a computer.
Connectors on the M-Bus side
M-Bus | Connector for connecting M-Bus line. | SH-02-5.08 |
Transmit | Indication of broadcasting on the M-Bus line. | green |
Receive | Indication of receiving on the M-Bus line. | yellow |
Overload/Short | Indication of overload or short circuit on the M-Bus line. | red |
- during overload the LED flashes alternately with Receive LED, I > 8mA |
- short circuit is indicated with the LED turned on permanently, resistance of the M-Bus line < 500Ω |
Connectors on the Power Supply and Ethernet side
Power | Connector for power supply and earth ground. | SH-02-5.08 |
Ethernet RJ45 | Connector for Ethernet. | RJ45 |
Power | Indication of correct power supply voltage. | green |
Link | 10Mbps connection speed. | orange |
100Mbps connection speed. | green |
Rx/Tx | Half-duplex | orange |
Full-duplex | green |
Web Interface
M-Bus meter table
Dimensions
|
|
|
|
|
|