Communication signals | A (+ Tx/Rx), B (- Tx/Rx), GND |
Protection | overvoltage protection TVS 600W |
Terminating resistors | A 1kΩ to +5V, B 1kΩ to GND, between A & B 120Ω - JUMPER |
Galvanic separation | 1kV from power supply, >1kV from the M-Bus line |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Number of devices that can be connected | 1 to 5 SLAVE devices, idle current max. 7.5mA |
Baud rate | 300 - 9600 bps |
Protection | - overvoltage protection TVS 1500W |
- electronic protection against overloads and short circuit on the communication line |
note: converter can withstand sustained short circuit on the communication line |
Galvanic separation | 1kV from power supply, >1kV from the RS485 line |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Recommended range of power supply voltages |
DC power supply | 9V to 34V |
AC power supply | 8V to 24V |
Protection | - overvoltage protection TVS 1500W |
- overcurrent protection with a 0.3A resettable PTC fuse |
Power consumption | 0.4W to 1.1W Depends on M-Bus line load and power supply. |
Connector | terminal block with plug-in connector for wires of up to 2.5 mm2 cross-section area |
Power - green | indication of connected supply voltage |
Transmit - green | indication of data broadcasting on the M-Bus line |
Receive - yellow | indication of data reception on the M-Bus line |
Overload/Short - red | indication of M-Bus line overload – flashing (idle current > 8mA) |
indication of short on the M-Bus line – turned on (resistance of the line < 500Ω) |
Operating range | -40°C to 70°C |
Mechanical design | aluminium box |
Mounting | 35 mm DIN rail (EN 50022 top hat rail) |
Dimensions: height x width x length | 33 x 57 x 87 mm - without connectors |
33 x 57 x 106 mm - with connectors (M-Bus and Power plug-in connectors in the terminal blocks) |
Protection classification | IP20 |
Weight | 125g |
EMC compatibility of the M-Bus converter has been tested according to the following industrial environment standards.
Standard | Test | Level |
EN 55011 | Power line - CONDUCTED EMISSIONS 10/150 kHz - 30 MHz | Class A |
EN 55011 | RADIATED EMISSIONS (Electric Field) 30 MHz - 1000 MHz | Class A |
|
Standard | Test | Level |
EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Contact discharge | ± 4 kV |
EN 61000-4-2 | ELECTROSTATIC DISCHARGE (ESD) - Air discharge | ± 8 kV |
EN 61000-4-3 | RADIATED RADIO-FREQUENCY ELECTROMAG. FIELD 80MHz - 1GHz | 10 V/m |
EN 61000-4-3 | RADIATED RADIO-FREQUENCY ELECTROMAG. FIELD 1.4GHz - 2GHz | 10 V/m |
EN 61000-4-3 | RADIATED RADIO-FREQUENCY ELECTROMAG. FIELD 2GHz - 2.7GHz | 3 V/m |
EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - Power line | ± 4 kV |
EN 61000-4-4 | ELECTRICAL FAST TRANSIENT/BURST - M-Bus, RS485 line | ± 4 kV |
EN 61000-4-5 | SURGE IMMUNITY - Power line. Common/differential mode. | ± 1 kV / ± 1 kV |
EN 61000-4-5 | SURGE IMMUNITY - M-Bus, RS485 line. Cable shielding. | ± 4 kV |
EN 61000-4-5 | SURGE IMMUNITY - M-Bus line. Common/differential mode.* | ± 4 kV / ± 2 kV |
EN 61000-4-6 | CONDUCTED DISTURBANCES, INDUCED BY RADIO-FREQUENCY | 10 V |
FIELDS 0.15MHz - 80 MHZ. Power line and M-Bus line. |
* test carried out at the request of the manufacturer.
The M-Bus port has an increased durability against overvoltage. Carrying out this type of test is not required with the use of shield cable.